96
14
Troubleshooting
Diagnostic procedure for check code
Check code
Operation cause
[9A]
1. Miswiring/Mispiping of indoor/outdoor units
Indoor unit miswiring/misconnection
2. Insufficient refrigerant
3. Blockage in pipe run
Investigate the check code.
Remove the cause, and check
miswiring again.
Wiring is correct.
Yes
Are there any other
check codes ?
Check miswiring according to conditions
in Table 1.
No
Was the outdoor unit stopped for
20 minutes or more before
checking miswiring ?
No
Yes
Is 9A displayed again ?
Insufficient refrigerant, miswiring
or blockage
No
No
Did you check miswiring
according to the temp.
conditions Table 1 ?
Stop the outdoor unit for 20
minutes or more, and then check
miswiring again.
Yes
Yes
Table 1
Cooling miswiring
Indoor
18 to 32 °C
Outdoor
15 to 43 °C
Check code
Operation cause
[9F]
1. Indoor unit PMV connection error/main unit error
Refrigerant circulation amount
2. TC1 sensor/TC2 sensor/TA sensor error
shortage judgement
3. Miswiring/Mispiping between indoor and outdoor
units
4. Blockage in pipe
Is indoor PMV normal ?
1. Connector connection
2. Wiring
3. Coil
4. Valve
5. Indoor PC board
Are the following sensors
normal? TC1, TC2, TA, Pressure
Is wiring correct ?
Repair indoor PMV.
Replace defective sensor.
No
No
Yes
Yes
Yes
Blockage or pipe breakage.
Modify wiring.
No
(Check with miswiring check function of the outdoor unit.)
Summary of Contents for A90-0132
Page 2: ...2 ...
Page 4: ...4 ...
Page 174: ......
Page 175: ......
Page 176: ...www toshiba aircon co uk MADE IN UK A90 0132 Revised June 2002 ...