86
14
Check code
Operation cause
[21]
1. Inverter high pressure SW error
Inverter high pressure SW
2. Inverter IOL (Inner Overload) operation
circuit alarm
3. Service valve closed
4. Outdoor fan, capacitor error
5. Indoor/Outdoor PMV blockage
6. Outdoor heat exchanger blockage
7. SV2 circuit blockage
8. Indoor – Outdoor communication error
9. Pd sensor error
10. Refrigerant over charge
Troubleshooting
Diagnostic procedure for check code
Does the inverter high pressure
switch operate?
Is the inverter high pressure
switch normal?
Is service valve fully open?
Does the outdoor fan operate?
Is there a problem with the
outdoor unit heat exchanger?
(1) Blockage of heat exchanger
(2) Short circuit
Il circuito di bypass della SV2 è
normale?
Is SV2 bypass circuit normal?
Refrigerant over charge
Blockage
Pipe breakage
Abnormal overload
Check parts.
If defective, replace.
Open service valve fully.
Remove cause.
Repair SV2 bypass circuit.
(Coil error, disconnection
of wiring, etc.)
Are the connections for the
capacitor and fan motor normal?
Is the high pressure sensor
characteristics normal?
See judgment flow of inverter IOL
operation circuit “E5”.
Repair defective part.
Replace high pressure sensor.
Check outdoor inverter PC board.
If defective replace board.
Is the inverter IOL
circuit normal?
Is circuit wiring normal?
Check and modify wiring
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No