Trial operation
Service support function
Function to start/stop (ON/OFF) indoor unit from outdoor unit
A function to start/stop the following indoor units by switch operation on the interface PC board is provided.
No.
Function
Outline
Clear set-up
(1)
Trial cooling
The modes of all the connected indoor units are
[Set-up]
operation
collectively changed to trial cooling operation modes.
Push SW04 for 2 seconds or more under condition
of SW01 “2”, SW02 “5”, SW03 “1”.
NOTE:
Control operation is the same as that of normal trial
[Clear]
operation from the remote controller
Returns SW01, SW02 and SW03 to “1”.
(2)
Collective
All the connected indoor units are operated
[Set-up]
operation
collectively.
Push SW04 for 2 seconds or more under condition
of SW01 “2”, SW02 “7”, SW03 “1”.
NOTE:
Operation contents match the set-up on the remote
[Clear]
controller.
Returns SW01, SW02 and SW03 to “1”.
Collective
All the connected indoor units are stopped
[Set-up]
stop
collectively.
Push SW05 for 2 seconds or more under condition
of SW01 “2”, SW02 “7”, SW03 “1”.
[Clear]
Returns SW01, SW02 and SW03 to “1”.
(3)
Individual
The specified indoor unit is operated.
[Set-up]
operation
To operate SW01 “16”, SW02 and SW03
NOTE:
Set to the indoor address No. (1 to 40), and push
Operation contents match the set-up on the remote
SW04 for 2 seconds or more.
controller.
Other indoor units stay as they are.
[Clear]
Returns SW01, SW02 and SW03 to “1”.
Individual
The specified indoor unit is stopped.
[Set-up]
stop
Setting SW01 “16”, SW02 and SW03 to the address
NOTE:
No. (1 to 40) of the indoor unit to be operated, push
Other indoor units are as they are.
push SW05 for 2 seconds or more.
[Clear]
Returns SW01, SW02 and SW03 to “1”.
NOTE:
This start/stop function is only to send the mode signals such as stop/operation mode, etc. from outdoor unit to indoor unit.