Troubleshooting
Diagnostic procedure for check code
Check code
Operation cause
[99]
1. Remote controller circuit connection error
Remote controller serial signal circuit alarm
2. Duplicated indoor No.1 units
3. Remote controller error
4. Indoor PC board error
Are A, B, C internal wires normal?
Check connection of wiring.
No
Yes
Is there a connection error?
Yes
No
Set SW01 to 1.
Avoid duplication of unit set-up to No.1.
Is SW01 set to No. 1
on the master unit?
Is SW01 duplicated?
Check indoor PC board.
If defective, replace.
No
No
Yes
Yes
Does the indoor unit operate?
Is the unit set-up No.1?
Make unit set-up No.1.
No
Yes
Is group operation performed?
Yes
No
Check indoor PC board.
If defective, replace.
Check remote controller PC board.
If defective, replace.
Does serial LED (Green)
D11 on the indoor PC board
flash?
Does serial LED (Orange)
D13 on the indoor PC
board flash?
No
Yes
No
Yes
No
Yes