148
19
Replacing the compressor
Compressor replacement procedure
Start
Was refrigerant recovery
work executed when
replacing the compressor ?
Extract oil from compressor.
Remove the failed compressor.
Recover refrigerant according to page 145
Refrigerant Recovery Method when replacing
compressor or by a refrigerant recovery device.
Remove parts.
Turn off power of the failed unit.
Install the compressor.
Check leakage of the failed unit.
Vacuum the failed unit.
Charge refrigerant.
Open valves fully
(Balancing, liquid, and gas pipes)
End