17
Parts specifications
Indoor units
Chassis: MM-N080
No.
PARTS NAME
TYPE
SPECIFICATIONS
1
Fan motor
SMF-230-34-4O
Output (rated) 34 W, 4 pole, 230 V, 1 phase, 50 Hz
2
Running capacitor – Fan motor
EEP2H155HQA107
AC 500 V, 1,5
μ
F
3
Pulse motor valve
EDM-B40YPTR-7B-A Capacity: 40
Chassis: MM-N056
No.
PARTS NAME
TYPE
SPECIFICATIONS
1
Fan motor
SMF-230-34-4D
Output (rated) 34 W, 4 pole, 230 V, 1 phase, 50 Hz
2
Running capacitor – Fan motor
EEP2W205HQA107
AC 450 V, 2,0
μ
F
3
Pulse motor valve
EDM-B40YPTR-7B-A Capacity: 40
Chassis: MM-N042
No.
PARTS NAME
TYPE
SPECIFICATIONS
1
Fan motor
SMF-230-34-4H
Output (rated) 34 W, 4 pole, 230 V, 1 phase, 50 Hz
2
Running capacitor – Fan motor
EEP2W205HQA107
AC 450 V, 2
μ
F
3
Pulse motor valve
EDM-B40YPTR-7B-A Capacity: 25
Chassis: MM-N028
No.
PARTS NAME
TYPE
SPECIFICATIONS
1
Fan motor
SMF-230-34-4H
Output (rated) 34 W, 4 pole, 230 V, 1 phase, 50 Hz
2
Running capacitor – Fan motor
EEP2H155HQA107
AC 500 V, 1,5
μ
F
3
Pulse motor valve
EDM-B25YPTF-7B-A Capacity: 25
Chassis: MM-N080, NN-N056, MM-N042, MM-N028
No.
PARTS NAME
TYPE
SPECIFICATIONS
4
Transformer
TT-03-1
DC 16.3 V – 0.5 A / AC 11.6 V – 0.15 A
5
Pulse motor
EDM-MD12TF-3
DC 12 V
6
Pressure sensor
150/100NH6-D
Power voltage DC 12 V
7
Sensor for room temperature
TA
Maximum input:
°C
25
50
38 mA at 25 °C
k
Ω
10
3.45
8
Sensor for heat exchanger
Tc1
Maximum input:
°C
-12
0
25
50
34 mA at 25 °C
k
Ω
62.3
32.8
10
3.6
9
Sensor for heat exchanger
Tc2
Maximum input:
°C
0
25
50
26 mA at 25 °C
k
Ω
34.6
10
3.4
10
Control PCB
CM**C02
AC 220 – 240 V
11
Power PCB
P**RC01
AC 220 – 240 V
4