140
(2) Collective start/stop (ON/OFF) function
This function is to start/stop (ON/OFF) the indoor units connected to an identical system collectively using the switch on the
interface PC board of the inverter outdoor unit.
Operation procedure
Power ON
Set the operation mode of the remote controller.
(If set-up is not executed,operation is performed under the present mode.)
(FAN, COOL)
Set SW01 to 2, SW02 to 7, and SW03 to 1 on the interface PC board of the
inverter outdoor unit.
Push the push-switch SW04 for 2 seconds or more on the interface PC
board of the inverter outdoor unit.
All the connected indoor units are operated collectively.
Push the push-switch SW05 for 2 seconds or more on the interface PC
board of the inverter outdoor unit.
After trial operation,return the display select switches SW01, SW02, and
SW03 on interface PC board of the inverter outdoor unit to 1.
Operation Check
(When the discharge temp.does not change even if
COOL is set on the remote controller, miswiring is
considered.)
Completion
Operation
Trial operation
Service support function
Stop
If an alarm has been already displayed as SW01 1,
SW02 1, SW03 1, return the status to normal according
to Troubleshooting, and then execute a trial operation.
18
SW01, 02, 03:
Rotary switch
SW04, 05:
Push switch
SW08:
Dip switch