13
Parts specifications
Outdoor units
COMPRESSOR
MODEL
MM-A0280HT
MM-A0224HT
MM-A0280HX
MM-A0224HX
MM-A0160HX
MM-A0280CT
MM-A0224CT
MM-A0280CX
MM-A0224CX
MM-A0160CX
Model name
MG1450CW-21B
YG1800CW-B1
YG1700CW-B1
YG890C-B1
Motor type
3-phase induction motor
Power supply
380-415 V, 3 ph, 50 Hz
Output (kW)
7.5
7.5
7.5
6.0
4.1
Pole (P)
2/2 (INV./Fixed)
2/2 (Fixed/Fixed)
2
Coil resistance (
Ω
)
1.18/2.25 (INV./Fixed)
2.25/2.25 (Fixed/Fixed )
2.250
Comp. oil name
NISSEKI
RB74AF
VG 74
Amount of oil (ml)
7500
7500
7500
7500
2000
Inner overload relay
Opens: 115±5°C
Closes: 93±10°C
4-WAY VALVE
MODEL
MM-A0280HT
MM-A0224HT
MM-A0280HX
MM-A0224HX
MM-A0160HX
Model name
CHV-0712
CHV-0712
CHV-0712
CHV-0712
CHV-0401
Coil specification
AC240V
AC240V
AC240V
AC240V
AC240V
MM-A0280HT, MM-A0224HT, MM-A0280HX, MM-A0224HX, MM-A0160HX
MM-A0280CT, MM-A0224CT, MM-A0280CX, MM-A0224CX, MM-A0160CX
PARTS NAME
SPECIFICATION
Fan motor
Model name
STF-200-350A
Motor type
1-phase induction motor
Power supply
AC 220 – 240 V. 1 phase, 50 Hz
Output (W)
400
Current (A)
4.81-5.89
Pole (P)
6
High pressure switch
Model name
INV = ACB-JB128
FIX = ACB-JA64
Operating pressure (mPa)
Operation: 3.2
Reset: 2.55
High pressure sensor
Model name
150NH4-H
Operating conditions (mPa)
0-3.33
Low pressure sensor
Model name
150NH4-L
Operating conditions (mPa)
0-0.98
Compressor case heater (fixed-speed only)
AC 240 V – 74 W
Accumulator case heater
AC 240 V – 29 W
Discharge temperature sensor
18.1 k
Ω
at 50 °C – 3.35 k
Ω
at 100 °C
Suction temperature sensor
34.6 k
Ω
at 0 °C – 10.0 k
Ω
at 25 °C – 3.4 k
Ω
at 50 °C
Pulse modulating valve (heat pump unit only)
L12A-03, DC 12 V
Pulse modulating valve (for cooling bypass)
A12A-15, DC 12 V
2-way valve
NEV-603DXF, coil 240 V
2-way valve
NEV-202DXF, coil 240 V
4
Summary of Contents for A90-0132
Page 2: ...2 ...
Page 4: ...4 ...
Page 174: ......
Page 175: ......