155
Replacing the interface PC board
Interface PC board replacement procedure
How to replace the interface PC board - MCC-1343-03
The service interface PC board is common to all MMS outdoor models.
Replace the PC board according to the following procedure:
(1) Turn off the power supply of the outdoor unit.
(2) Remove all the connectors and fasten terminals connected to the interface PC board.
(Remove the connectors without grasping the leads)
(3) Remove the interface PC board from the mounting clips.
(4) Cut the jumper link of the service PC board according to the table below:
Inverter unit - heat pump model
Outdoor model
Electrical box label
Jumper No.
Service PC board label
J-02
J-05
J-06
J-07
J-08
J-09
J-22
MM-A0280HT
MMY-MP1001HT8-INV
cut
-
-
-
-
-
-
MMY-INV
MM-A0224HT
MMY-MP0801HT8-INV
cut
-
-
cut
cut
cut
-
MMY-INV
Fixed-speed unit - heat pump model
Outdoor model
Electrical box label
Jumper No.
Service PC board label
J-02
J-05
J-06
J-07
J-08
J-09
J-22
MM-A0280HX
MMY-MP1001H8-E-P
cut
cut
-
-
-
-
-
MMY-E-P
MM-A0224HX
MMY-MP0801H8-E-P
cut
cut
-
cut
cut
-
-
MMY-E-P
MM-A0160HX
MMY-MP0601H8-E-P
cut
cut
cut
cut
-
cut
-
MMY-E-P
Inverter unit - cooling only model
Outdoor model
Electrical box label
Jumper No.
Service PC board label
J-02
J-05
J-06
J-07
J-08
J-09
J-22
MM-A0280CT
MMY-MP1001HT8-INV
cut
-
-
-
-
-
cut
MMY-INV
MM-A0224CT
MMY-MP0801HT8-INV
cut
-
-
cut
cut
cut
cut
MMY-INV
Fixed-speed unit - cooling only model
Outdoor model
Electrical box label
Jumper No.
Service PC board label
J-02
J-05
J-06
J-07
J-08
J-09
J-22
MM-A0280CX
MMY-MP1001H8-E-P
cut
cut
-
-
-
-
cut
MMY-E-P
MM-A0224CX
MMY-MP0801H8-E-P
cut
cut
-
cut
cut
-
cut
MMY-E-P
MM-A0160CX
MMY-MP0601H8-E-P
cut
cut
cut
cut
-
cut
cut
MMY-E-P
(5) From the tables above confirm the jumper status and PC label matches the required outdoor unit.
(6) Insert the PC board into the electrical control box ensuring the PC board is secured by the 7 supporting clips.
(7) Insert the connectors and the fasten terminals.
(8) Check there is no insertion error and that all components are vertical.
(9) Replace electrical control box cover and outer painted panel.
(10) Turn on power supply and check the operation of the outdoor unit is normal.