Self diagnostic display information
Outdoor units
Outdoor unit information data display (Displayed on each outdoor unit)
SW03
SW02
SW01
Displayed content
1
1
1
Check code
A [U1] to [U5]: Outdoor unit number (1 = Inverter)
B [—]: Normal time (No error)
A check code is displayed in abnormality
<SW04>:
Push function:
Only fan of unit in which an error occurred operates.
<SW04> and
<SW05>:
Push function: Only fan of normal unit operates.
<SW05>:
Push function: Fan operation function is interrupted.
2
Type of installed compressor
A [U1] to [U2]: Outdoor unit number
B [A]: Fixed-speed 2 in 1; [b]: Fixed-speed 2 compressor
[C]: Fixed-speed single, [d] Inverter (2 in 1)
3
Operation mode
A —
B [C]: Cooling operation, [H]: Heating operation
4
Outdoor unit capacity
A [6], [8], [10]: 6, 8, 10 HP
B [HP]
5
Compressor operation command
A [1.-]: No. 1 compressor stop status, [1.1]: During operation
For inverter, the frequency code is displayed: [00] to [FF]
B [2.-]: No. 2 compressor stop status, [2.1]: During operation
<SW04>:
Push function: Inverter frequency data is displayed in decimal notation.
<SW05>:
Push function: Release of frequency data display in decimal notation.
6
Outdoor fan operation pattern
A [FP]
B [0] to [16]: 0 wave (stop) to 16 waves (All waves)
7
Compressor back-up
A [C1]: Under No. 1 compressor back-up set-up
B [C2]: Under No. 2 compressor back-up set-up
8
—
A —
B —
9
Control valve output
A
B
SV2: OFF
H. O
2. 0
SV2: ON
H. O
2. 1
10
SV3A: ON/SV3B: OFF/SV3C: OFF
3. 1
0 0
SV3A: OFF/SV3B: ON/SV3C: OFF
3. 0
1 0
SV3A: OFF/SV3B: OFF/SV3C: ON
3. 0
0 1
11
SV41: ON/SV42: OFF
4. 0
1 0
SV41: OFF/SV42: ON
4. 0
0 1
12
—
—
—
13
—
—
—
14
PMV A1 + PMV A2 opening
[00] to [500]: 0 to 1000 pulse
0
0 P
15
PMVB opening
[00] to [500]: 0 to 500 pulse
0
0 P
16
Oil level judgement status
A [OL]
B [ ]: Initial display, [FF]: Oil judgement start status,
[AO]: Adequate,[A1]: Shortage,[ A2 to A4]: Detection error
<SW04>:
Push function: Oil level judgement control forcible start
(Detection starts after timer countdown)
<SW05>:
Push function: Oil level shortage status/continuous counter display
(Displayed for several seconds)
NOTE:
The push-switch function operates by input from the inverter unit.
Summary of Contents for A90-0132