116
Troubleshooting
Diagnostic procedure for check code
Check code
Operation cause
[dE]
1. Indoor unit in automatic addressing mode
Indoor address undefined
2. Indoor unit PC board set-up error
3. Defective indoor unit PC board
4. Communication noise interference
While this check code is displayed, wait for a moment. When the address is defined, the operation is
automatically reset. However, if the check code does not disappear 20 minutes after the power source was
turned on, a fault is considered. Check the following items.
•
Fault check of indoor unit PC board
•
Source check of communication noise interference
•
Incorrect set-up of jumper options on indoor unit PC board
Check code
Operation cause
[dF]
1. Outdoor unit in automatic addressing mode
Outdoor address undefined
2. Defective indoor unit interface PC board
3. Communication noise interference
While this check code is displayed, wait for a moment. When the address is defined, the operation is
automatically reset. However, if the check code does not disappear 20 minutes after the power source was
turned on, a fault is considered. Check the following items.
•
Fault check of outdoor unit interface PC board
•
Source check of communication noise interference between outdoor units.