Control circuit configuration
Indoor units
(4) Switch positions at shipment from the factory
Switch No.
Function
Description
Position at shipment
from factory
SW01
Indoor unit No.
Group operation control set-up
Set-up 1: Master unit
2 to 16: Slave units
SW02
Network address set-up
For contents of address set-up, see the next page.
SW03
TA adjust
No. 1
ON
Normal
No. 2
OFF
Normal
SW06
Ceiling height
No. 1
OFF
Normal
No. 2
OFF
Normal
When height of ceiling exceeds 2.7 m set No. 1 to ON.
SW07
Central control
switching
ON
Communication error
(Non relay)
OFF
(Normal)
Communication OK
No. 2
OFF
Normal
SW08
Indoor HP set-up
Factory set
For contents of switch set-up, see section (5)
ON
Address set-up by remote controller is
unavailable.
OFF
Address set-up by remote controller is
available.
No. 7
No. 1
13