69
12
Self diagnostic display information
Outdoor units
(3) Outdoor cycle data display (Displayed on each outdoor unit)
SW03
SW02
SW01
Displayed content
2
1
1
Pressure sensor Pd
Pressure sensor data is displayed with (MPaG).
A
B
H
2
Pressure sensor Ps
L
3
Temperature sensor TD1
Temperature sensor data is displayed with (°C).
Symbol
t
d
1
•
Symbol display and data display are alternately
Data
4
Temperature sensor TD2
exchanged every several seconds.
Symbol
t
d
2
•
Data is displayed in the part marked with
Data
5
Temperature sensor TS
symbol [
].
Symbol
t
s
•
If data is negative data, [
-
] is displayed.
Data
6
Temperature sensor TE1
Symbol
t
E
1
Data
—
—-
—
—
—
—
—
—
8
Temperature sensor TK1
Symbol
t
F
1
Data
9
Temperature sensor TK2
Symbol
t
F
2
Data
10
Temperature sensor TK3
Symbol
t
F
3
Data
(4) Outdoor cycle data display (Displayed on each outdoor unit)
*
Outdoor cycle data display is used when the fixed-speed unit information is displayed on the 7 segment section of the
inverter unit.
SW03
SW02
SW01
Displayed content
1 to 4
1
3
Check code
A [U2] to [U5]: Outdoor unit number (set-up with SW03)
B [—]: Normal time (No error)
A check code is displayed in abnormality
2
Type of fixed-speed compressor
A [U2] to [U5]: Outdoor unit number (set-up with SW03)
B [A]: Fixed-speed 2 in 1 compressor
[b]: Fixed-speed 2 compressor
[C]: Fixed-speed single compressor
3
Fixed-speed unit capacity
A [U2] to [U5]: Outdoor unit number (set-up with SW03)
B [6], [8], [10]: 6, 8, 10 HP
4
Fixed-speed compressor operation A [6], [8], [10]: 6, 8, 10 HP
command
B [10]: No. 1 compressor start/No. 2 compressor stop status
[01]: No. 1 compressor stop/No. 2 compressor start status
5
—
A [U2] to [U5]: Outdoor unit number (set-up with SW03)
For inverter, the frequency code is displayed: [00] to [FF]
B —
6
—
A [U2] to [U5]: Outdoor unit number (set-up with SW03)
B —
7
Oil level judgement status
A [U2] to [U5]: Outdoor unit number (set-up with SW03)
B [ ]: Normal time, [L]: Shortage
NOTE:
The outdoor unit number is set by selecting SW03.
SW03
Outdoor unit number
7 segment display A
1
Outdoor unit No. 2 (Fixed-speed 1)
[U2]
2
Outdoor unit No. 3 (Fixed-speed 2)
[U3]
3
Outdoor unit No. 4 (Fixed-speed 3)
[U4]
4
Outdoor unit No. 5 (Fixed-speed 4)
[U5]
Summary of Contents for A90-0132