89
14
Is the system set-up of the slave
outdoor unit being completed?
Is the power supply of the
slave outdoor unit turned on?
Is communication cable
connected correctly between
the outdoor units?
Is the BUS communication
connector (CN601) of the
outdoor unit at the server
connected?
Check interface PC board.
Clear the alarm, and the operation starts (*1).
Turn on the power supply.
Check the connection of the connector.
(BUS communication connector: CN601)
Check connection of communication cable.
Yes
No
No
No
No
Yes
Yes
Yes
Troubleshooting
Diagnostic procedure for check code
Check code
Operation cause
[8d]
1. Outdoor unit system set-up
Reduction in the No. of
2. Outdoor unit power source
connected outdoor units
3. Connection error of communication cable between
outdoor units
4. Connection error of BUS communication
5. Interface PC board error
( *1) How to clear the alarm
Set SW01/SW02/SW03 on interface PC board of
the master outdoor unit to 2/16/1 respectively,
and push SW04 for 5 seconds.
(Display on the 7 segment display: [Er.] [CL]).
Check code
Operation cause
[8E]
1. No. of connected outdoor units over limit
Outdoor unit connection
2. Connection error of communication cable
over limit
between outdoor units
Is the No. of connected
outdoor units 5 or below?
Is the communication cable
connected between outdoor
units?
Check interface PC board.
Check connection of communication cable.
The maximum number of outdoor units is 5.
No
No
Yes
Yes