134
18
Trial operation
Procedure and summary of trial operation
(3) Cooling operation check
Start
Check each
indoor unit
consecutively.
Set the operation mode to COOL by
pushing the operation switch for 5
seconds or more, and then check “L”
is displayed.
Trial operation from outdoor
unit is also available.
Is there cool air discharge ?
Is air circulation good ?
Operate all the units concurrently.
Is temp. difference of suction/
discharge air good ?
Is the supply voltage good
(220V 240V) ?
Is the operation current within
±15% of the catalogue
current value ?
(Max. Hz operation)
Is the operation
pressure normal ?
Normal
Check operation status of the compressor.
This air conditioner is attached with
reactivation delay timer, so the operation
restarts 2 minutes 30 seconds after it
stopped.
Check louvre direction.
Check the supply power voltage.
Check power cable dia.
Check overload of indoor /outdoor temperature.
Check pipe length and refrigerant amount.
Check the compressor operation Hz, and outdoor fan
operation status.
Is there an abnormal sound of the compressor ?
(NOTE 3)
(NOTE 1)
(NOTE 2)
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
[
]