Self diagnostic display information
Outdoor units
System information data display (Displayed on the inverter unit only)
The combination of rotary switches SW01, SW02 and SW03
display the following info:
SW03
SW02
SW01
Displayed content
3
1
1
Use refrigerant
Type of refrigerant used is displayed
A
B
•
In case of R-22 model
22
•
In case of R-407C model
40
7C
2
Outdoor system capacity
A [8] to [46]: 8 to 46 HP
B [HP]
3
No. of connected outdoor units
A [1] to [5]: 1 to 5 units
B [P]
4
No. of connected indoor units
A [0] to [40]: 0 to 40 units
B [P]
5
No. of operating indoor units
A [0] to [40]: 0 to 40 units
B [P]
6
—
A —
B —
7
Release control operation
A [r]: Normal operation, [r1]: Under release control
B —
8
Oil equalizing pattern
A [OL]
B [P]: Normal operation, [P1] to [P3]: Oil equalizing patterns 1 to 3A
9
—
A —
B —
10
Refrigerant/oil recovery operation
A [C-]: Normal operation, [C1]: Under cooling oil recovery control
B [H-]: Normal operation, [H1]: Under heating refrigerant recovery
11
Automatic address
A [Ad]
B [ ]: In normal time (Automatic address set-up completes)
[11]: Under automatic address set-up
12
—
—
13
—
—
14
—
—
15
—
—
16
—
—
SW01, 02, 03: Rotary switch
SW04, 05:
Push switch
SW08:
Dip switch