65
Outline of control
Indoor units
Item
Operation explanation and applied data, etc.
Remarks
6. Air volume
(1) By the command from the remote controller or the central controller, “HIGH”, “MED.”, • During stop
control
“LOW”, or “AUTO” operation is permissible.
operation, control to
(2) While air volume is in AUTO mode, the air volume is changed according to the
prevent cold draft is
difference between Ta and Ts.
determined by TC2.
LOW
MED
HIGH
COOL
HEAT
Ultra low
compressor
off
HIGH
MED
LOW
+2
+1
Ts
+1
Ts
-1
-2
7. Freeze
(1) In cooling operation, the air conditioner operates as described below based upon
prevention
temp. detected by TC1 and TC2 sensors.
control (Low
• When “J” zone is detected for 5 minutes, the command frequency becomes
temp. release)
“S0” to the outdoor unit.
• In “K” zone, the timer count is interrupted, and held.
• When “I” zone is detected, the timer is cleared and the operation returns to
normal operation.
• When the command frequency becomes S0 with continuation of “J” zone,
operation of the indoor fan in LOW mode occurs until it reaches the “I” zone.
It is reset when the following conditions are satisfied.
1)
TC1
≥
12 °C and TC2
≥
12 °C
2)
30 minutes after the air conditioner has stopped.
(°C)
Q
P
a
K
I
J
TCI
TC2
P
10
-12
Q
0
-15
8. Cooling
When the indoor units stand by, thermostat is OFF, or unit operates with “FAN” mode,
• Only for 4-way/2-
refrigerant/
PMV of the indoor unit is opened by a certain degree when the cooling oil/heating
way ceiling cassette
Heating oil
refrigerant recovery signal is received from the outdoor unit.
type, operate the
recovery
indoor fan inter-
control
mittently during the
recovery operation.
9. Short
(1) For 5 minutes after the operation has started, the operation is continued even if
intermittent
entering thermostat-OFF condition.
operation
(2) However, if the thermostat has been turned off by changing the set-up temp., the
compensation
thermostat is OFF with even the above condition. The protective control has priority.
control
10. Drain pump
(1) During “COOL” operation, the drain pump operates.
• When CHECK code
control
(2) When the float SW operates, the compressor stops and the drain pump operates.
“0b” occurs, the
(3) When the operation of the float SW continues for 2 minutes, a check code is
outdoor units stop
generated.
and “STANDBY” is
displayed on the
remote controllers
of all the indoor
units.