114
14
Replace SV3C valve.
The protective stop is due to operation in
high ambient temperature.
Clear the alarm, and start the operation.
No
Is there a leakage of
SV3C valve ? (*1)
Yes
Is it an operation in high
ambient temperature ?
(Outside temp. 43°C
or more)
Check interface PC board.
Yes
Is the resistance value
characteristics of TK1 sensor
normal ?
No
Yes
Sensor error.
No leakage
Troubleshooting
Diagnostic procedure for check code
Check code
Operation cause
[dC]
1. SV3C valve leakage
SV3C valve leakage detection
2. TK1 sensor resistance value characteristics error
3. Outdoor unit operation in high external temperatures
( *1) SV3C valve leakage check procedure
1.
Remove SV3C coil and start a trial operation.
2.
During operation, check the temperature at secondary side of SV3C valve (A).
If the temperature is high (equivalent to discharge temperature), leakage from SV3C valve is
considered.
Replace SV3C valve.
Oil
separator
Sensor TK1
SV3C
Valve
strainer
Check joint
Capillary
Strainer
Accumulator
Check
joint
Capillary
Sensor
TK2
Compressor
Valve
SV3A
Oil tank
Check
valve
Check
valve
Oil
removal
valve
Valve
SV3B
Check
valve
Balancing pipe valve
Strainer
Strainer
•
(A)
Strainer