4: User defined V/F curve.
Fmax
output
voltage
output frequency
0
3
2
1
Fig. 6-11 V/F curve
P4.01 Base voltage
Setting range: 0~440V
P4.02 Base frequency
Setting range: 10.00~ 400.0Hz
Basic V/F characteristic of TMP series is shown in Fig. 6-12. Base
Frequency F
BASE
is the
output frequency corresponding to the rated output voltage U
N
. Its range is 10 to 400Hz.
Generally, F
BASE
should be selected according to rated frequency of the motor. In some special
case, it can be selected according to requirement. In this condition, both motor V/F characteristic
and output torque should be considered.
output Frequency
output
voltage
U
N
0
F
MAX
F
BASE
Fig. 6-12 Base voltage and frequency
P4.03 Intermediate voltage 1
Setting range:0
~
P4.04
P4.04 Intermediate voltage 2
Setting range:P4.03
~
100% (Inverter’s rated voltage)
P4.05 Intermediate frequency 1
Setting range:0~P4.06
P4.06 Intermediate frequency 2
Setting range: P4.05~400.0Hz
P4.07 Torque boost
Setting range:0
~
20%(Inverter’s rated voltage)
In order to compensate the torque drop at low frequency, the inverter can boost the output
voltage in the low frequency zone, which is shown in Fig. 6-13.