TMP High Performance Vector Control Inverter User Manual
43
P2.27
Jump frequency range
0.00~20.00 Hz
0.00
67
+
P2.28
FWD/REV dead time
0.0~3600s
0.5
68
+
P2.29
REV prohibited
0: REV enabled
1: REV disabled
0
69
+
P2.30
Carrier frequency
2.0~12.0KHz
3.0
70
+
P2.31
Zero
frequency
threshold
0.0~400.0Hz
0.00
71
+
P2.32
Zero
frequency
hysteresis
0.0~400.0 Hz
0.00
72
+
P2.33
Droop control
0.00-10.00Hz
0.00
73
+
P3 Group
motor parameters
P3.00
Motor rated power
0.4~999.9KW
Drive’s
rated power
74
+
P3.01
Motor rated voltage
0~440V
380V
75
+
P3.02
Motor rated current
0.1~999.9A
Drive’s
rated value
76
+
P3.03
Motor rated frequency
1.00~400.0Hz
50.00
77
+
P3.04
Motor rated speed
1~9999RPM
1440
78
+
P3.05
Motor auto-tuning
0
:
No operation
1
:
static auto tuning
2
:
overall auto- tuning
0
79
+
P3.06
Stator resistance
0.001-20.00%
Motor
parameter
80
+
P3.07
Rotor resistance
0.001-20.00%
Motor
parameter
81
+
P3.08
Self
inductance
1
.
000-9
.
999
Motor
parameter
82
+
P3.09
Leakage
inductance
0
.
001-1
.
000
Motor
parameter
83
+
P3.10
Exciting current with
0.0~999.9A
Motor
84
+