TMP High Performance Vector Control Inverter User Manual
52
1
:
2400BPS
2
:
4800BPS
3
:
9600BPS
4
:
19200BPS
5
:
38400BPS
PC.01
Data format
0: 8,N,2 for RTU
(
MODBUS
)
1: 8,E,1 for RTU
(
MODBUS
)
2: 8,O,1 for RTU
(
MODBUS
)
3: 7,N,2 for ASCII (MODBUS
)
4: 7,E,1 for ASCII
(
MODBUS
)
5: 7,O,1 for ASCII
(
MODBUS
)
6
:
8,N,1 free communication format
7
:
8,E,1 free communication format
8
:
8,O,1 free communication format
9: 8,N,2 for RTU
(
MODBUS
)
MASTER
0
215
+
PC.02
Local address
1~32
,
0 is the broadcast address
1
216
+
PC.03
Communication
timeout detect
0
,
No detection
2.0~10.0s
0
217
+
PC.04
Response delay
2~1000ms
218
+
PC.05
EEROM
Store
selection
0
:
Store
1
:
no store function
0
219
+
Pd Group
Faults and protection parameters
Pd.00
Motor
overload
protection mode
0:
No protection
1:
Common motor protection
2:
Variable frequency motor protection
1
220
+
Pd.01
Motor
overload
protection factor
20.0~150.0%
100.0
221
+
Pd.02
Over
voltage
stall
selection
0: Disabled
1: Enabled
1
222
+
Pd.03
Stall
over
voltage
point
120.0~150.0%
120.0
223
+
Pd.04
Selection of overload
0: Detect at constant speed and alarm
0
224
+