TMP High Performance Vector Control Inverter User Manual
51
PA.10
Differential time
0.00
,
no differentiation
0.01~99.99s
0
195
#
PA.11
Sample cycle
0.01~99.99s
0.1
196
#
PA.12
Error limit
0.0~15.0%
0.0
197
#
PA.13
Level
of
abnormal
feedback signal
0~100%
50
198
#
PA.14
Detection
time
of
abnormal
feedback
signal
0
:
No detection
0.1~3600s
0.0
199
#
PA.15
reserved
0
200
+
PA.16
PID Sleep control
0:
No sleep function;
1:
Internal waking up,
2.
External input terminal
0
201
+
PA.17
Delay time of sleepin
0~3600s
0
202
+
PA.18
Sleeping frequency
0.00~400.0Hz
0.00
203
+
PA.19
Delay time of waking
0.0~60.0s
0.0
204
+
PA.20
Waking value
0.0~100.0%
100.0
205
+
Pb GROUP
Traverse operation parameters
Pb.00
Traverse mode
0:
Auto mode
1:
Manual mode
0
206
+
Pb.01
Preset
traverse
frequency
0.00~400.0 Hz
0.00
207
#
Pb.02
Hold time of preset
traverse frequency
0.0~3600s
0.0
208
#
Pb.03
Preset
central
frequency
0.00~400.0 Hz
0.00
209
#
Pb.04
Travers amplitude
0.0~50.0% (Pb.03)
0.0
210
#
Pb.05
Step frequency
0.0~50.0% (Pb.04)
0.0
211
#
Pb.06
Traverse cycle
0.1~999.9s
10.00
212
#
Pb.07
Rise time of triangular
wave
0.0~100.0% (Pb.06)
50.0
213
#
PC Group
485 communication parameters
PC.00
Baud rate selection
0
:
1200BPS
3
214
+