TMP High Performance Vector Control Inverter User Manual
30
GND
Analog grounding
Internal isolated with COM
Relay
output
A1/B1/C1
Relay output
A1
-
B1
:
Normally open
C1
-
B1
:
Normally closed
Contact capacity: 250VAC/1A, 30VDC/1A
Note:
﹡
If the user connects adjustable potentiometer between
+
10V and GND, the resistance of the
potentiometer shall be no less than 5
kΩ,
Note:
1. The arrangement sequence of the control circuit terminals is as follows:
3.9 Lectotype of Control Circuit Peripheral Devices
Terminal number
Terminal
screw
Tightening
torque
(N·m)
Wire
specification
mm
2
Wire type
+10V
、
AI1
、
AI2
、
485+
、
485−
、
AO1
、
AO2
、
GND
M3
0.5
~
0.6
0.75
Twinning shielding
cable
+24V
、
X1
、
X2
、
X3
、
X4
、
X5
、
X6
、
X7/DI
、
CM
、
Y1
、
CM
、
A1
、
B1
、
C1
M3
0.5
~
0.6
0.75
Shielding cable
3.10 Description of Jumper Function
Jumper selecting switch in Fig.3-7:
AI2
V
I
AO2
V
I
485
ON
OFF
Name
Function
Leave-factory
setting
AI2
I is the current input
(0~20mA), V is the voltage input (0~10V)
0~20mA
AO2
I is the current input
(0~20mA), V is the voltage input (0~10V)
0~20mA
485
485 terminal resistor selection: ON: there is 100Ω terminal resistor, OFF: there
is no terminal resistor
There is no terminal
resistor