50
SC-F70
SC-F70
PID Operation Operating Instructions
No.
Name
Description
Symbol
Factory
Setting
Range
-
5.0 to 105.0%
±
10% of the
measurement
span
[Measurement
unit]
±
10% of the
measurement
span
[Measurement
unit]
±
10% of the
measurement
span
[Measurement
unit]
0: Slow
1: Medium
2: Fast
0.0
0
0
0
0
Notes:
1. The soft start time units can be set by the parameter PG10/SVGr, item No. 3 (see page
79). The factory default units are hour.minute.
2. The parameter is set for heating in the heating, cooling PID operation.
3. The Integral time I, and the Differential time d for cooling are automatically set to the
same values as these parameters for heating.
4. Refer to "3.5 Compensation for Control Responsiveness" on page 51 for selecting a
value.
Manual reset
for cooling
Dead zone
(see Note 2)
Dead zone for
cooling
Control
responsiveness
selection
(See Note 4)
Sets the manual reset value
for cooling control output.
* This item is displayed when
P
π
0.0, Pc
π
0.0, and I=0 in
heating, cooling PID
operation.
[Auto-tuning PID operation ]
Adds db value to a target set
value and compensates the
target set value virtually in
On and Off actions (P=0.0).
* This item is displayed when
P=0.0.
[Heating, cooling PID
operation ]
Provides a control dead zone
between the heating
proportional band and the
cooling proportional band.
Provides a control dead zone
between the heating
proportional band and the
cooling proportional band.
* This item is displayed in
heating, cooling PID
operation.
Sets the responsiveness
when the control setting has
been changed.
Cr
Mrc
db
15
16
17
18
dbc