58
SC-F70
SC-F70
PID Operation Operating Instructions
4.2 Remote Area Switching Operation
This diagram shows the wiring of external contacts for remote area
switching.
There are three ways to use these four points (Di1 - Di4), as defined in
the parameter PG06/DiGr item 1 (diS value). See page 76.
diS value
0: MAN/AUT switching plus area selection
1: LOC/REM switching plus area selection
2: Area selection
To start remote operation, set the mode to REM.
You can set REM mode either by setting the diS value to 1 and using the
contact for it, or you can set it using the control panel. Select the diS
value for the operation you plan to use.
The next diagram shows how to allocate the contact points for the area
number and switching functions.
MAN/AUT SW
COM (—)
4 Di2
2 Di3
1 Di4
∑
diS=0
∑
diS=1
∑
diS=2
12
13
14
15
16
8 Di1
COM (—)
4 Di2
2 Di3
1 Di4
Di1
Function
Function
Terminal
Terminal
Terminal
Function
A r e a
No.
12
13
14
15
16
LOC/REM SW
COM (—)
4 Di2
2 Di3
1 Di4
A r e a
No.
Di1
12
13
14
15
16
Back panel terminals
1
2
3
4
5
6
33
34
35
36
37
38
22
23
24
25
26
27
12
13
14
15
16
17
Di1
COM
(-)
Di2
Di3
Di4
No voltage contact
A r e a
No.
External contacts