PID Operation Operating Instructions
Action
Analysis
∑
Using temperature sensor (TR1)
1. Reconfirm that the temperature value indicated on the
thermometer is correct.
2. Confirm that the settings for the sensor in the
parameter PG02:
PVI : 410
PVF : 0
PVb : 0
Sensor
3. Meter the sensor resistance between wire No.19 and
20 or 21, after detaching them from the terminals.
* The TR1 resistance value is affected by the ambient temperature.
To know the correct resistance for a given condition, refer to the
document that has the Pt100 standardized resistance values.
∑
If the resistance is adequate,
have the controller serviced.
∑
If the resistance reading differs
largely from standard
resistance, have the sensor
serviced.
∑
If the reading is zero
W
or
infinity, go to the next step.
4. Remove the sensor cables from the sensor terminal, and
measure the sensor resistance between A and B as shown.
Ohmmeter
∑
If the resistance is adequate,
have the sensor cable serviced.
If the resistance is not
adequate, replace the sensor.
RTD
19
20
TR1
21
A
B
B
or
A
B
B
Sensor Terminal
∑
If the setting is not right,
correct it.