PID Operation Operating Instructions
3. Even if power restoration mode has been selected, mode selection with the external
contact input, if used, overrides.
4. The control output becomes 0.0 for both heating and cooling in the heating, cooling
PID operation.
5. This value becomes the preset value of the heating control output in the heating,
cooling PID operation. The preset value of the cooling control output becomes 0.0.
8. PG09/AtGr (Auto-tuning)
The item of this group is not displayed in the heating, cooling PID
operation.
Setting limiter
lower limit
Setting limiter
upper limit
Soft start time unit
Soft start or change
rate limiter
selection.
Deviation range
for Up deviation
LED
Deviation range for
Down deviation
LED
Setting lock
Lower
limit
Upper
limit
0
0
5%
¥
span
0
Sets limiters for the lower and
upper limits to restrict the
range of target setting.
Selects the unit for the AREA
setting soft start.
Selects which is used for the
AREA setting: a soft start
time or a setting change rate
limiter.
Sets the deviation range
within which the Up and
Down deviation LED will
light up.
Selects which settings are
locked.
1
2
3
4
5
6
7
9. PG10/SVGr (Settings)
Range
Description
No.
Symbol
Name
Factory
setting
Same as
measurement
range.
(See Note)
SVL < SVH
0: Hour.Minute
1: Minute.Second
0: Soft start
1: Setting
change rate
limiter
0~
measurement
span
(See Note)
0: All unlocked
1: Parameter
settings
locked
2: All locked
Range
No.
Symbol
Factory
setting
Name
Description
1
Auto-
tuning bias
Normally Auto-tuning on-off
control is based on the target
setting. When an Auto-tuning bias
is set, Auto-tuning is based on the
target setting plus the Atb value.
±
measurement
span or 9999
0
Note: Use the same unit specified in the measurement input unit.
Atb
SSL
LoK
dVd
dVu
tMS
SVH
SVL