PID Operation Operating Instructions
Procedure-1 Verifying the Valve Actions in MAN Mode
Step
Action
1
2
DISP
PARA
AREA
ENT
A.SEL
DISP
MODE
Measurement value
PV
SC-F70
PARA
AREA
ENT
A.SEL
DISP
MODE
Measurement value
Control Output
PV
SC-F70
3
4
PARA
AREA
ENT
A.SEL
DISP
MODE
PV
SC-F70
<
<
<
<
<
<
∑
Make sure that the AUT and REM lamps are off.
If either is on, change the mode to LOC/MAN by referring to "Mode Key
Operation Flow" on page 25.
∑
Set the control output to 0 %.
1
Press several times until the Symbol
Display shows OUT.
2
Press or key to set the control
output value to 0.0 (%).
Note:
Continuous pressure on or will
change the value rapidly.
∑
Turn on power supply and air supply to the actuator.
1
Gradually increase and decrease the control output
by pressing the or key.
2
Check that the control valve moves (see Note 1 on
next page) as follows:
Control Output Control Valve Movement
Reverse Movement
Forward Movement
Increase
open
close
Decrease
close
open
Note:
Continuous pressure on or will
move the valve actuator rapidly.
<
<