PID Operation Operating Instructions
4. Other Precautions
1) Use M3.5 crimp terminals with insulating sleeves.
2) Use a time-lag fuse rated for 250 V, 1 A, if you install an external
fuse.
3) Refer to this wire specification table when selecting cables.
Recommended Wire Specifications
Power line
Grounding wire
In, out signal
Wire Specifications
Type
Cabtyre
Cabtyre
2-wire or 3-wire
shielded
AWG*
16 or larger
14 or larger
18 or larger
Diameter (mm
2
)
1.25 or larger
2.00 or larger
0.75 or larger
Warning
Do not turn on power supply to the value with which this controller
will be used until instructed to do so in section 3.2 "Test Operation".
!
* American Wire Gage