78
SC-F70
SC-F70
PID Operation Operating Instructions
7. PG08/ErGr (Operation)
0
0
0
0
0.0
0
0
No.
Symbol
Factory
setting
Selects the control output
value during a measure-
ment input error, analog
setting input error, or
area selection input error.
∑
Operates only in AUT
mode.
Selects the action taken
when an error occurs
during the auto-tuning
process.
∑
Not displayed in the heating
cooling PID operation.
Selects the initial
control output value at
power restoration.
Selects the control
output value when the
mode is changed from
AUT to MAN.
Sets the control output
preset value used for
No. 1, 2, and 3 in this
table. (Note 5)
Selects the initial mode
when power is restored.
Selects the start point
for soft start control at
startup or when mode
has been changed from
MAN to AUT.
1
2
3
4
5
6
7
Name
Description
Range
Operation
during input error
(Note 1)
Operation during
auto-tuning error
( Notes 1, 2)
Output value
after power
restoration
(Note 1)
Output value for
MAN mode
change
(Note 1)
Preset control
output
Operation after
power restoration
(Note 3)
Starting point
for soft start
0: Held at the value just
before error occurred
1: Held at the preset value
2: Held at output limiter
lower limit
(Note 4)
3: Held at 0%
0: Held at value just
before AT was started
1: Held at preset value
2: Held at output limiter
lower limit
3: Held at 0%
0: 0%
1: Preset value
2: Output limiter lower
limit (Note 4)
3: Value just before power
was cut off
0: Bump-less transition
1: Preset value
2: Output limiter lower
limit (Note 4)
3: 0%
-5.0 to 105.0%
0: LOC/MAN
1: LOC/AUT
2: REM/MAN
3: REM/AUT
4: Mode when power
was interrupted
0: Start at measured
value
1: Start at zero point
Note: 1. No matter what is specified in this item, the control output is limited by the setting of
the output upper or lower limiter. However, the control output becomes 0% when the
control output is a relay output and in On-Off action (P=0.0).
2. When 1, 2, or 3 is specified in this item, and an Auto-tuning error occurs, an error code
(E11 to E13) is displayed, until the key is pressed.
DISP
IPE
AtE
lot
PrV
MMV
MSL
SFt