7
SC-F70
SC-F70
PID Operation Operating Instructions
1.2 Setting Feature Jumpers
The following feature jumpers can be set to customize your controller.
∑
To select measurement input type
∑
To select analog input (used only with the analog input feature).
These jumpers are set at the factory to your order specifications.
If BOTH of the following conditions are met, there is NO need to check
the jumper setting. You can go to "1.3 Attaching to the Panel" directly.
1. The sensor to be used is a pressure transmitter MBS33M (from
Danfoss A/S), KH15 (from Nagano Instrument Corp.), or a
temperature sensor TR1 obtained from TLV.
2. Remote analog setting operation is not used.
Warning:
Do not try to use the controller without setting the jumpers correctly
according to your mode of operation. If you do, an unexpected
malfunction may arise.
Use these steps to set the jumpers
1. Make sure the controller is turned off.
2. Remove the controller body from its
case (see Figure 1).
1. While pushing the stopper tab 1
upward,
2. Pull the body by the frame of the
display panel 2 .
3. To identify the two groups of jumpers,
see Figure 2.
Warning:
To prevent damage, do NOT touch any metal parts on the boards
when you do the next step.
4. Using tweezers, remove and insert the jumpers at the appropriate
positions. Refer to Figure 2 for the jumper positions to select
Measurement Input and Analog Input.
Stopper
PA
RA
AR
EA
EN
T
A.S
EL
DIS
P
MO
DE
PV
SE
T
AU
T
RE
M
AT
AL1
AL2
AL3
AL4
FAI
L
SC
-F
70
[Figure 1]
!
!
2
1