39
SC-F70
SC-F70
PID Operation Operating Instructions
Step
Action
5
<
PARA
AREA
ENT
A.SEL
DISP
MODE
PV
SC-F70
PARA
AREA
ENT
A.SEL
DISP
MODE
PV
SC-F70
In this example,
the temperature
rises 120˚C when
the control output
is set to 55.5%.
6
7
8
∑
You have completed the verification of valve actions in MAN mode.
If you found any problem with the controller, control valve, or sensor during this test
procedure, refer to the troubleshooting guides in "7. Troubleshooting" on page 84.
Note 1: This description assumes that the control valve actuator moves in a reverse direction.
When the actuator moves in a forward direction, the valve behaves in the opposite
way.
<
<
∑
Press to set the control output below 0.
∑
Ensure that supplying steam to the equipment is safe.
Then gradually open the shutoff valve.
∑
Because the control valve is shut (Note 1), check that
no steam flows to the secondary side of the control
valve.
∑
By pressing and , adjust the
control output value gradually to reach and stay on a
target set value in everyday operation.
∑
In the same manner, adjust the control output to obtain
several other target set values .
∑
Record the control output values and respective target
set values for quick reference for later manual
operation.
∑
You can use the controller for production with this
procedure.
∑
Decrease the control output to zero percent by pressing
.
∑
Make sure that the control valve has been closed (see
Note 1).
<