35
SC-F70
SC-F70
PID Operation Operating Instructions
2. PG03/MVGr (Control output)
Range
Description
No.
Symbol
Name
Factory
setting
0
1
0
0.1% of
measure-
ment
span
0.0
0: Current
output
1: Relay output
0: Reverse
1: Forward
0 ~10%of
measurement
span
[measurement
unit]
0.0 ~100.0
%/second
Specifies output type for the
control output and for the
cooling control output.
* otc is displayed in the heating,
cooling PID operation.
Used to select the type of
control output (forward or
reverse).
* Displayed in the auto-tuning
PID operation.
* In the heating, cooling PID
operation, the movement is
always reverse for heating,
and always forward for
cooling.
Sets the hysteresis for the
ON-OFF operation.
* HSc is displayed in the
heating, cooling PID
operation.
Imposes restrictions on the
amount of change per unit of
time when control output
values are changed.
* The change rate limiter is
OFF when the value is set to
0.0.
Control output
type
(see Note 1)
Control output
type for cooling
Control output
forward or reverse
selection
Hysteresis
(see Note 1)
Hysteresis for
cooling
Output change rate
limiter
oS
otc
ot
1
2
4
3
5
HSc
HS
6
or