PID Operation Operating Instructions
DC current output
1. Output:
4-20 mA
2. Load resistance range:
600
W
maximum
3. Output impedance:
5 M
W
minimum
4. Output accuracy:
±
0.1% of span
5. Output resolution:
11 bit minimum
* When a relay output is selected for the first control output type, the
first control output becomes the transmission output 3.
Relay output
1. Contact:
1c contact
2. Output:
AC250V 3A (resistor load)
3. Electric life:
More than 300,000 times(rated load)
4. Proportional period:
1~100 seconds, variable
* When a current output is selected for the first control output type,
the first control output becomes the alarm output 3 (AL3).
* Either the DC current output or the relay output can be specified
as the first control output type.
9.5.2 Second Control Output (OUT2)
This is the cooling control output in the heating, cooling PID operation.
This output becomes the transmission output 2 or the alarm output 4
(AL4), respectively, in Auto-tuning PID operation.
DC current output
1. Output:
4-20 mA
2. Load resistance range:
600
W
maximum
3. Output impedance:
5 M
W
minimum
4. Output accuracy:
±
0.1% of span
5. Output resolution:
11 bit minimum
* When a relay output is selected for the second control output type,
the second control output becomes the transmission output 2.
Relay output
1. Contact:
1a contact
2. Output:
AC250V 3A (resistor load)
3. Electric life:
More than 300,000 times(rated load)
4. Proportional period:
1~100 seconds, variable
* When a current output is selected for the second control output type,
the second control output becomes the alarm output 4 (AL4).
* Either the DC current output or the relay output can be specified
as the second control output type.