111
SC-F70
SC-F70
PID Operation Operating Instructions
9.7 Transmission Output
(1) Number of output points:
3 points maximum
*The number of transmission
output points decreases, if the
control output is a current output.
(2) Output types (selectable):
Measured value, set value,
deviation, or control output
(3) Output signal:
DC 4 mA to 20 mA
(4) Load resistance:
600
W
maximum
(5) Output scaling setting range
1. Measurement value (PV): Same as measurement input range
2. Deviation (DEV):
±
measurement span or -1999 to 9999
3. Set value (SV):
The same as for the measurement
input range
Note: Decimal point position is the same as for the measurement
range, for 1, 2, and 3.
4. Control output (OUT):
0.0 to 100.0%
(6) Output accuracy:
±
0.1% of span
(7) Output resolution:
11 bits minimum
9.8 External Contact Input
(1) When external analog setting input function is installed:
1. Number of input points:
1
2. Input method used:
No-voltage type contact
Resistance when OPEN:
500 k
W
minimum
Resistance when CLOSED:
10
W
maximum
3. Voltage when OPEN:
DC 5 V
4. Functions (selectable):
Operation mode switching,
MAN/AUT or LOC/REM