57
SC-F70
SC-F70
PID Operation Operating Instructions
®
®
®
®
®
Remote Analog Input Operation
The next procedure describes how to run the controller using remote
analog input.
∑
Set the feature jumper to select current or voltage for the analog input. See
"Analog Input Selection Jumper" on page 8.
∑
Set all 6 items of PG05. See page 75.
∑
Set the diS parameter of the PG06. See page 76.
∑
Set the target value on the external analog input signal.
Note: Do not change the mode to REM before the target value has been set.
Otherwise, an unexpected analog value will result, or a set value input
error will occur.
∑
Set the mode to REM.
Do the following on the operation panel (diS = 0):
LOC
Æ
REM switching (Operation panel)
1
Press twice.
* LOC and REM (blinking) appear on the Symbol and SV display,
respectively.
2
Press .
* The REM lamp of the status indicator turns on, and the panel changes to the display
state.
or
Do the following if you use the external contact (on back panel) (diS = 1):
LOC
Æ
REM switching (External contact)
1
If Dil contact point is open, close it; if closed, open and close it.
∑
Set the mode to AUT.
Do the following on the operation panel (diS = 1):
MAN
Æ
AUT switching (Operation panel)
1
Press once.
* MAN and AUT (blinking) appear on the Symbol and SV display,
respectively.
2
Press .
The AUT lamp of the status indicator turns on, and the panel changes to the display
state.
or
Do the following when you use the external contact (on back panel) (diS = 0):
MAN
Æ
AUT switching (External contact)
1
If Dil contact point is open, close it; if closed, open and close it.
∑
Once this procedure is completed, only analog input value set by the external
device will be accepted by the controller.
Note: The analog input signal fluctuation must be less than
±
0.1 % F.S. If the
fluctuation exceeds this, the controller may accept the fraction as a new set
value, which can cause a hunting problem in the valve actuator.
Step
Action
3
2
1
MODE
ENT
MODE
ENT
7
6
4
5