8. Seek the PID constants using the following
equations:
Proportional band
P=167
¥
Kp
¥
L/T
Integral time
I=T
Differential time
D=0.5L
9. Entering the PID values determined in the previous step, run the
controller in AUT mode and verify its control responsiveness.
Note:
If the results do not meet your requirements, change the PID values by
referring to "3.6 PID Constants Fine Tuning Method" on page 52.