PID Operation Operating Instructions
∑∑∑∑∑
Using the Alarm
This procedure describes how to use the alarm.
Step
Action
∑
Wire the back panel terminals to set up the alarm for AL1 to AL4 (see page 62).
∑
Determine and set the parameter PG04 for the type of alarm, the excitation, the
hysteresis, and the timer. (see page 73)
Note: The Exciting or Non-exciting parameter controls the alarm relay
contacts as follows:
In both cases, Normally closed points act conversely.
∑
Determine and set the alarm values in the AREA you plan to use.
∑
Start your control operation.
* If needed, create the alarm condition artificially to test your alarm setup.
∑
Monitor the alarms.
2
1
Exciting
Normally open contacts close when alarm is activated
Non-exciting Normally open contacts open when alarm is activated
3
4
5
Hysteresis delay
Pressure
Alarm setting
(Upper limit)
Alarm output
Timer delay
Timer: Delays the alarm output activation.
Hysteresis: Delays the alarm output deactivation.
Use of these timer and hysteresis delays provides additional control to
prevent frequent alarm activation due to the unstable pressure.