Choosing a building drying program automatically binds inputs and external sensors according to
the table below to reduce the amount of necessary manual setup. These settings can of course be
changed, if so desired.
Programs – Building drying
Program 688 – Only room drying
A room‘s humidity is to be reduced. As soon as the absolute humidity
outdoors
falls below the hu
-
midity
indoors
, a fan is activated.
The fan runs, if
• the absolute humidity outdoors falls below the absolute humidity indoors
and
• the optional interval operation („timer“) is active
and
• the relative humidity
indoors
exceeds the minimal humidity
min1
.
A1 = S5 > min1 & S1 > (S2 + diff1)
No time programs can be set up for this program.
Program 689 – Room drying and minimum temperature monitoring
A room‘s humidity is to be reduced. If it becomes too cold in the ventilated room, the fan is deacti
-
vated.
The fans runs, if
• the absolute humidity outdoors falls below the absolute humidity indoors
and
• the room temperature is high enough (to prevent excessive cooling in cold seasons)
and
• the optional interval operation („timer“) is active
and
• the relative humidity
indoors
exceeds the minimum humidity
min1
A1 = S5 > min1 & S1 > (S2 + diff1) & S3 > min3
No time programs can be set up for this program.
Input
Ext. Sensor
Value
S1
E1
Absolute humidity indoors
S2
E2
Absolute humidity outdoors
S3
E3
Temp. indoors
S4
E4
Temp. outdoors
S5
E5
Relative humidity indoors
S6
E6
Relative humidity outdoors
necessary settings:
factory setting
min1
diff1
... minimum relative humidity indoors
... minimum difference in humidity indoors/outdoors
62/60%
1,0/0,5 g/m
3
necessary settings:
factory setting
min1
diff1
min3
... minimum relative humidity indoors
... minimum difference in humidity indoors/outdoors
... minimum temperature indoors
62/60%
1,0/0,5 g/m
3
10/9 °C