49
Program 544 – Cascade: S1 -> S2 -> S3 -> S4
Program 544:
Pump
A1
runs, if:
•
S1
exceeds the threshold
min1
• and
S1
is greater than
S2
by the difference
diff1
• and
S2
has not exceeded the threshold
max1
.
The charging pump
A2
runs, if:
•
S2
exceeds the threshold
min2
• and
S2
is greater than
S3
by the difference
diff2
• and
S3
has not exceeded the threshold
max2
.
The charging pump
A3
runs, if:
•
S3
exceeds the threshold
min3
• and
S3
is greater than
S4
by the difference
diff3
• and
S4
has not exceeded the threshold
max3
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = S2 > (S3 + diff2) & S2 > min2 & S3 < max2
A3 = S3 > (S4 + diff3) & S3 > min3 & S4 < max3
necessary settings:
max1
max2
max3
min1
min2
min3
diff1
diff2
diff3
... limit CYL1 S2
... limit CYL2 S3
... limit CYL3 S4
... activation temp. coll. S1
... activation temp. CYL1 S2
... activation temp. CYL2 S3
... coll. S1 - CYL1 S2
... CYL1 S2 - CYL2 S3
... CYL2 S3 - CYL3 S4
à
A1
à
A2
à
A3
à
A1
à
A2
à
A3
à
A1
à
A2
à
A3