113
Run-on time
Especially solar and heating pumps with long hydraulic pipelines may have issues with con
-
stant turning on and off again over longer times when attempting to start up. This is espe
-
cially disadvantageous for modern high-efficiency pumps. Such behavior can be avoided by
specific usage of the speed control or by setting up a run-on time.
This setting is to be made specifically for each output.
If usual automatic regulation would switch off an output, it will
keep on running for the duration of the run-on time before actually
deactivating. If the output is reactivated before the run-on time has
passed, it will not have been deactivated. Manual mode ignores
the run-on time.
Blocking time
This setting is to be made specifically for each output.
If an output is deactivated by usual automatic regulation, the
blocking time must elapse before the output may be reactivated.
Manual mode ignores the blocking time.