Collector cooling function
Using this function, a solar system‘s cylinder can be cooled overnight to allow it to take in
warmth again the next day.
If the chosen sensor (cylinder temperature) exceeds the specified temperature, the speci
-
fied outputs will be activated within the specified time window until the temperature is un
-
derrun again.
Enable
Collector cooling function Yes/No
(FS = No)
Monitored
sensor
The (cylinder) sensor that is to be moni
-
tored.
Maximum
value
This threshold must be exceeded by the
monitored sensor in order for the cooling
function to activate.
Affected out
-
puts
These outputs are activated, once the
chosen sensor exceeds the specified
threshold within the defined time win
-
dow. If a control output is assigned to the
output, the analogue level for full speed
will be output.
Options: Combination of all outputs (1-5)
Start
Time of day, beginning at which the affected outputs may
be activated. (FS = 22:00)
Range: 00:00 to 24:00 in 1 minute steps
End
Time of day, beginning at which the affected outputs may
be activated. (FS = 06:00)
Range: 00:00 to 24:00 in 1 minute steps