All pr1:
Charging pump
A3
runs, if:
•
S1
exceeds the threshold
min1
• and
S1
is greater than
S4
by the difference
diff3
• and
S4
has not exceeded the threshold
max3
or
•
S3
exceeds the threshold
min2
• and
S3
is greater than
S4
by the difference
diff3
• and
S4
has not exceeded the threshold
max3
or
•
S5
exceeds the threshold
min3
• and
S5
is greater than
S4
by the difference
diff3
• and
S4
has not exceeded the threshold
max3
.
A3 = (S1 > (S4 + diff3) & S1 > min1 & S4 < max3)
or
(S3 > (S4 + diff3) & S3 > min2 & S4 < max3)
or
(S5 > (S4 + diff3) & S5 > min3 & S4 < max3)
necessary settings:
max1
max2
max3
min1
min2
min3
diff1
diff2
diff3
... limit CYL1
S2
... limit CYL1
S2
... limit CYL2
S4
... activation temp. heat source
S1
... activation temp. boiler
S3
... activation temp. CYL1
S5
... heat source
S1
- CYL1
S2
... boiler
S3
- CYL1
S2
... heat source
S1
- CYL2
S4
... boiler
S3
- CYL2
S4
... CYL1
S5
- CYL2
S4
à
A1
à
A2
à
A3
à
A1, A3
à
A2, A3
à
A3
à
A1
à
A2
à
A3
à
A3
à
A3