Program 656 – DHW preparation incl. circu burner request
Only practical with speed control activated!
(
Absolute value control: mode „Inverted“ input S1, Differential v.c. mode „Normal“ sensors S3 and S1
)
Program 656:
Pump
A1
runs, if:
• Flow switch
S5
detects flow. The nominal value for the speed control (absolute value
control) of pump
A1
is specified for
S1
.
Pump
A2
runs, if:
•
S3
exceeds the threshold
min1
• and
S3
is greater than
S4
by the difference
diff1
• and
S4
has not exceeded the threshold
max1
.
Output
A3
is activated, if
S3
falls below the threshold
min3
.
Output
A3
is deactivated (dominantly), if
S2
exceeds the threshold
max3
.
A1 = flow switch (S5) = ON
A2 = S3 > (S4 + diff1) & S3 > min1 & S4 < max1
A3 (on) = S3 < min3 A3 (off) = S2 > max3
All pr1:
Circulation pump
A2
is only activated, if flow switch
S5
is
ON
(
A1
= ON), in
addition to basic regulation.
All pr2:
The burner request (
A3
) is regulated using only sensor
S3.
A3 (on) = S3 < min3 A3 (off) = S3 > max3
(dominant)
All pr4:
Pump
A1
runs, if:
• Flow switch
S5
or pump
A2
is active.
A1 = A2 or flow switch S5 = ON
necessary settings:
max1
max2
min1
min3
diff1
... limit circulation return
S4
... burner req. off CYL
S2
... activation temp. CYL
S3
... burner req. off CYL
S3
... CYL
S3
- circ. return
S4
à
A2
à
A3
à
A2
à
A3
à
A2