42
All pr1:
The charging pump
A1
runs, if:
•
S1
exceeds the threshold
min1
• and
S1
is greater than
S4
by the difference
diff1
• and
S4
has not exceeded the threshold
max1
.
The charging pump
A2
runs, if:
•
S5
exceeds the threshold
min2
• and
S5
is greater than
S3
by the difference
diff2
• and
S3
has not exceeded the difference
max2
.
Output
A3
is activated, if
S5
falls below the threshold
min3
.
Output
A3
is deactivated (dominantly), if
S4
exceeds the threshold
max3
.
A1 = S1 > (S4 + diff1) & S1 > min1 & S4 < max1
A2 = S5 > (S3 + diff2) & S5 > min2 & S3 < max2
A3 (on) = S5 < min3 A3 (off) = S4 > max3
All pr2:
Additionally, the charging pump
A2
is activated if the cylinder temperature
S3
(CYL2) falls below the boiler temperature
S1
by the difference
diff3
.
The charging pump
A2
runs, if:
•
S5
exceeds the threshold
min2
• and
S5
is greater than
S3
by the difference
diff2
• and
S3
has not exceeded the threshold
max2
.
or
•
S1
exceeds the threshold
min1
• and
S1
is greater than
S3
by the difference
diff3
• and
S3
has not exceeded the threshold
max2
.
A2 = (S5 > (S3 + diff2) & S5 > min2 & S3 < max2)
or
(S1 > (S3 + diff3) & S1 > min1 & S3 < max2)
All pr4:
The burner request (
A3
) is regulated only via sensor
S5.
A3 (on) = S5 < min3 A3 (off) = S5 > max3
(dominant)
All pr8:
The burner request (
A3
) is regulated only via sensor
S4.
A3 (on) = S4 < min3 A3 (off) = S4 > max3
(dominant)
Combining additions
+4
and
+8
is not permitted. An attempt to set this up (P460) will result
in the program number resetting to
+4
(P452).
necessary settings:
max1
max2
max3
min1
min2
min3
diff1
diff2
diff3
... limit CYL1
S4
... limit CYL2
S3
... burner req. off CYL1
S4
... activation temp. boiler
S1
... activation temp. CYL1
S5
... burner req. on CYL1
S5
... boiler
S1
- CYL1
S4
... CYL1
S5
- CYL2
S3
... see all pr2
à
A1
à
A2
à
A3
à
A1
à
A2
à
A3
à
A1
à
A2