12
Differential control – Programs
Program 0 – Simple solar system (factory settings)
S3 only used in pr1
Program 0:
Pump
A1
runs if:
•
S1
is greater than threshold
min1
w
and
S1
is greater than
S2
by the difference
diff1
• and
S2
has not exceeded threshold
max1
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
All Pr1:
In addition, if
S3
exceeds the threshold
max2
, pump
A1
is deactivated.
All Pr4: Simple drain-back solar system with valve
This program may only be selected if the drain-back function (
Expert level/Drain-back)
is ac
-
tivated.
The basic settings are the same as with program 0:
A valve on output 3 prevents the heat transfer medium from flowing out of the solar panel
during the day.
Once the filling time has elapsed, the valve connected to
A3
is switched
on.
If the pump
A1
is switched off due to the
temperature difference
, the valve
A3
will remain
switched on for another 2 hours.
If the excess temp. limiter or frost protection are activated, the sun radiation value goes be
-
low 50W/m
2
(only if a radiation sensor is used) or if the low water level protection detects a
low volume flow after the filling time, the valve is closed
immediately.
All Pr1:
In addition, if
S3
exceeds the threshold
max2
, pump
A1
is deactivated.
necessary settings:
max1
max2
min1
diff1
...
limit CYL
S2
...
see all programs
+1
...
activation temp. coll.
S1
...
coll.
S1 -
CYL
S2
à
A1
à
A1
à
A1
necessary settings:
max1
max2
min1
diff1
...
limit
CYL S2
...
see programs
1
or
5
...
see program
0
...
coll
S1 -
CYL
S2