64
Heating circuit control - Programs
All heating circuit programs (except program groups 816 and 976 as well as other stated
exceptions) require the following settings:
Program 800 – Heating circuit with up to 2 heat sources
A1 = S4 > min1 & (Heating circuit = active)
A2/A3 = Mixer
If no room sensor is in use, the room influence in the menu point
Expert level/Mixer
must be
set to
0.0%
.
Overview
Technician level:
Time/Date
Menu
Parameters
Mode (preferably
Auto
)
Basic parameters
Time programs
Heat curve
Expert level:
Set flow temp. at +10°C
and
at -20°C
or
Slope
Menu
Programming settings
Program (number)
Flow temperature
min
and
max
R
oo
m sensor pres
e
nt (Y/N)
Frost protection conditions
Use S4 (only P800 - 802)
Time program set values (Y/N)
Menus
Shutdown conditions
&
Mixer
Mixer selection (only P832 and above)
S1...
Room sensor
A1...
Heating circuit pump
S2...
Temperature outdoors
A2...
Mixer OPEN
S3...
Heating circuit flow
A3...
Mixer CLOSE
S4...
Cylinder top
S5...
Boiler