10
„Step by Step“ Setup guide
The following guide might give you instructions on setting up the device, but it is of utmost
importance to read the entirety of the instruction manual – especially the chapters „Pro
-
grams“ and „Operation“.
Level
1
Choose a hydraulic diagram based on the sketches of system dia
-
grams. Mind the arrow diagram, as well as the the program exten
-
sions „+1“, „+2“ and such, as far as they are specified in the diagram.
2
Choose a program based on its number. It may be feasible to use
one or more program extension such as „+1“ or „+2“ to optimize your
system‘s regulation.
3
Connect the sensors to the inputs, as well as pumps, valves etc. to
the outputs according to the chosen program. If used, connect the
data link (DL-Bus), the CAN-Bus and the control outputs.
4
Expert
Access the Expert level using the access code
64
and input your cho
-
sen program‘s number under „Program settings“.
5
Technician
Setting up the priority allocation in the sub-menu
Technician/Param
-
eters/Priority ranking
.
6
Technician
Enter the necessary setting values
max, min, diff
according to the list
of
„necessary settings“
below your chosen program‘s diagram.
7
Technician
Enter the time, date and summer time properties.
8
Technician
If required, specify time programs under
Time program
.
9
Technician
Menu
Manual Operation:
the choices „
Manual/ON
“ and „
Manual/OFF
“
offer the possibility to set outputs to be turned permanently
on
or
off
in order to check their connection. It‘s crucial to set the outputs back
to „Auto“ after you‘re done checking their functionality.
If the chosen program uses control outputs or if they‘ve been set up
manually, they can be set up to „
Manual/ON“
(= 10V or 100% PWM)
or „
Manual/OFF“
(= 0V or 0% PWM). Alternatively, you can choose a
specific voltage or PWM-percentage to be output. Don‘t forget to set
the outputs back to
Auto
after checking their functionality.
10
Expert
Outputs can be crossed out, if so desired. Find the option under
Crossout.
11
Expert
If you‘re not using the standard type PT1000 temperature sensors,
you must change your inputs‘ type of sensor in the
Sensor menu
.
12
Expert
If so desired, activate additional functions like
starting function, cool
-
ing function, heat meter
etc.
13
Check the displayed sensor measurements on whether or not they‘re
plausible. Disconnected or incorrectly parameterized sensors display
a value of 9999,9°C.