153
Outputs
In this menu, each used output has its own sub menu, in which
each can be given a designation that has no influence on opera
-
tion. Below that, settings for run-on time and blocking time can be
found (further details below). Additionally, several infos and sta
-
tistics are displayed, such as mode (Auto/Manual), and meter
readings for running hours and impulses („total“, „today“ and „pre
-
vious day“ for each) and a button for both meters to delete the
measurements of „today“. Before that, the button „Delete total
meter readings“ is found, which resets all meter readings back to
zero.
Blocking protection
Idle circulating pumps (e.g.: heating pumps in the summertime) may have troubles starting-
up as a result of corrosion. Solution: Periodically (e.g. every 7 days) activating the pump for
a few seconds.
Warning!
For programs with heat exchangers (e.g. program 384) both the primary and sec
-
ondary pumps must be switched on for blocking protection to avoid frost damages.
Enable
Blocking Yes/No (FS = No)
Interval time
If the chosen output has not been active for
the duration specified here, it will be activated
for the duration specified under Pump run
time.
Start time
Time of day at which the outputs are acti
-
vated. (FS = 15:00)
Pump run
time
Pump run time in seconds. The chosen out
-
puts will be activated for this duration
(FS = 15s)
Affected out
-
puts
Specifying the outputs which are to be acti
-
vated by the block protection. If the output has
a control output assigned to it, the variable for
maximum speed will be output by it.
Possible settings: Combination of all outputs
(FS = - - - - -)