20
Program 144 – Solar system with layered cylinder charging
Layered systems are only practical if the speed control is activated
(Absolute value control system: Mode „Normal“ and sensor input S1)
Program 144:
The solar pumps
A1
run, if:
•
S1
exceeds the threshold
min1
• and
S1
is greater than
S2
by the difference
diff1
• and
S2
has not exceeded the threshold
max1
.
The three-way valve
A2
switches
upwards
if:
•
S3
exceeds the threshold
min2
•
or,
if
S3
falls below
min2
,
S3
is greater than
S4
by the
difference
diff2
• and
S4
has not exceeded the threshold
max2
.
A1 = S1 > (S2 + diff1) & S1 > min1 & S2 < max1
A2 = (S3 > min2 or S3 > (S4 + diff2)) & S4 < max2
Program 145:
If
S4
has reached the threshold
max2
, the rapid warm-up phase is completed and the speed
control is blocked, which achieves optimal efficiency.
If Control Output A4 is activated, the analogue level for maximum speed will be output. Con
-
trol Output A5 is not affected and continues regulating.
necessary settings
max1
max2
min1
min2
diff1
diff2
... limit CYL
S2
... limit CYL
S4
... activation temp. coll.
S1
... activation temp. HE
S3
... coll.
S1
- CYL
S2
... HE
S3
- CYL
S4
à
A1
à
A2
à
A1
à
A2
à
A1
à
A2
Summary of Contents for UVR65